BLL 20 kV (24)

Products

BLL 24 kV 1X 62 FEAL TRESKIKT

Nexans ref. 21048898 - Country ref. 0105104

  • Packaging: Drum (1000m)
  • Conductor cross-section: 62 mm²
  • Nominal outer diameter: 15.5 mm
  • Approximate weight: 34.0 kg/100m

 

BLL 24 kV 1X 99 FEAL TRESKIKT

Nexans ref. 21054998 - Country ref. 0105105

  • Packaging: Drum (1000m)
  • Conductor cross-section: 99 mm²
  • Nominal outer diameter: 18.2 mm
  • Approximate weight: 50.0 kg/100m

 

BLL 24 kV 1X159 AlMgSi TRESKIKT

Nexans ref. 21056898 - Country ref. 0105106

  • Packaging: Drum (1000m)
  • Conductor cross-section: 159 mm²
  • Nominal outer diameter: 21.9 mm
  • Approximate weight: 64.5 kg/100m

 

BLL 24 kV 1X241 AlMgSi TRESKIKT

Nexans ref. 21055398 - Country ref. 0105107

  • Packaging: Drum (1000m)
  • Conductor cross-section: 241 mm²
  • Nominal outer diameter: 25.5 mm
  • Approximate weight: 90.1 kg/100m

 

Description

Description

Standards

  • International
    EN 50182; EN 50397

BLL is a non-compacted longitudinally water blocked by swellable tape, 1-leading line designed according to SS 424 14 32. The conductor is of different material depending on cross-section: Cross-section 62 and 99 mm² is made of FeAl.  The cross-sections 159 mm² and 241 mm² exist in AlMgSi type Al 7. The cable may maximum be loaded to a conductor temperature 70°C. The conductor is covered with PE and of one layers with a black weather proof PE. The line is marked manufacturer / type / year+month / metre marking.

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

 

Testing

The conductor is tested in accordance with SS-EN 50397 and 50182.

 

Quality and environmental management system

Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded
Insulation
PE
Colour
Black
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Operating voltage
20 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Usage characteristics

Usage characteristics

Bending factor when laying
15 (xD)
Bending factor when installed
10 (xD)
Minimum installation temperature
-20 °C
Maximum operating temperature
70 °C
Short-circuit max. conductor temperature
200 °C
Weather resistance
Good
Water proof
Longitudinal

Resources

Resources

Selling & delivery Information

BLL is delivered in lengths of 1000 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close