FQQ 450/750 V (CPR)

Description
The cable may be used for permanent installation on ladders, directly in walls, concrete, in conduits or ducts. For use indoors and outdoors but not in ground or water. The cable have protection against exposure of UV-light.

Description
Description
FQQ is a halogen free, HFFR-insulated and HFFR-sheathed house wiring cable with circular, stranded copper conductors. The cable is designed according to SS 424 02 19-5. The conductors have resistance and number of wires according to IEC 60228 class 2. The cores are identified by colours according to HD 308. Cables with 7 core are numbercoded, (1-6 and yellow/green).The cable has an extruded filler. The sheath is marked. type/manufacturer/year+month/metre marking. FQQ meets the requirements for flammability class Dcas2d2a2 according to CPR and have protection against exposure of UV-light according to HD 626 S1 part 2.5.1. The conductor insulation shall be protected against UV light that can occur for example in light fixtures and light signs. The cable is certified by Intertek SEMKO.
Lifemark(TM) recycling marking
The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.
Certification
Certifeid by Intertek SEMKO.
Quality and environmental management system
Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Conductor shape | Circular |
Conductor flexibility | Stranded class 2 |
Insulation | HFFR |
Outer sheath | HFFR (polyolefin) |
Colour | White |
Halogen free | Yes |
Usage characteristics | |
Minimum installation temperature | -10°C |
Recommended minimum installation temperature | 0°C |
Maximum operating temperature | 70°C |
Short-circuit max. conductor temperature | 150°C |
Smoke density | IEC 61034 |
Gases corrosivity | IEC 60754-2 |
Bending factor when installed | 6(xD) |
U.V resistance | Yes |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Selling information
Declaration of Performance
Declaration of Performance No: 1000519-SEGR
- Certification Date: 26/07/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 3
- Notified body : 0366
- Declared performance: Reaction to fire Dca -s2,d2,a2 according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
14141198-412-05 | 0406688 | FQQ 450/750 V 5G6 |
14141498-412-05 | 0406689 | FQQ 450/750 V 5G10 |